- メール
- 電話番号
-
アドレス
Building 3, Jibang Technology Park, No. 8 Jishan New Road Street, Tianhe District, Guangzhou City
Guangzhou Dongyi Automation Technology Co., Ltd
Building 3, Jibang Technology Park, No. 8 Jishan New Road Street, Tianhe District, Guangzhou City
Multi functional operator instrumentAs a supporting product for PID regulators or DCS systems, it is used for manual adjustment or as a backup instrument. The output signal is a current and voltage signal with positive and negative effects. One way to regulate input signals, used to receive signals transmitted from PID regulators or DCS systems. Can be connected with DC current and DC voltage. The main display window displays the operation output values, and the secondary display window can display the adjustment input signals, operation output values, or manual/automatic status through parameter selection. Welcome to consult with all users.
Multi functional operator instrumentProduct Introduction
Basic specifications
project |
specification |
|
power supply voltage |
ACpower supply |
100~240 V AC 50/60 Hz |
AC/DCpower supply |
10~24V AC 50/60 Hz;10~24V DC |
|
power consumption |
ACpower supply |
7 VAbelow |
AC/DCpower supply |
AC:6 VAfollowing;DC:5Wbelow |
|
Allowable voltage variation range |
The voltage of the power supply90%~110% |
|
insulation resistance |
≥100MΩ(500V DC MEGABenchmark) |
|
insulation strength |
2000V AC (Test conditions:50/60Hz,1Minutes) |
|
anti-interference |
IEC61000-4-2(Electrostatic discharge))Grade III IEC61000-4-4(Electric Fast Transient Pulse Group), Level III IEC61000-4-5(Surge), Level III |
|
Protection level |
IP65(Product front panel protection)(GB/T42-2008) |
|
runtime environment |
ambient temperature |
-30~60℃(Save:-40~65℃) |
ambient humidity |
35~85 %R•HNo condensation |
|
Installation location |
Indoor, height<2000m |
|
■ Enter specifications
project |
specification |
Measure and control speed |
0.1second |
basic error |
±0.2 %F•S |
display range |
-1999~9999 |
Display specifications |
double4bitLEDDisplay (Main Display Window)+Second display window) |
Æ Note:Please refer to the input signal type description for details Input signal and display explain.
■ Operation output specifications
project |
specification |
|
Q1 |
current output(4~20)mAThe(0~10)mAThe(0~20)mA |
Photoelectric isolation, Resolution:1/10000Load capacity:600Ω |
Q2 |
voltage output(0~5)VThe(1~5)V |
|
Q3 |
Voltage output(0-10)V |
|
■ Optional specifications
project |
specification |
||||
|
alarm output |
160×80size |
T1~T2 |
1~2The output of the alarm relay is normally open+Normally closed dual contacts |
250V AC/3A resistive load |
|
96×96size |
T1~T2 |
1~2Point alarm relay output, all with normally open contacts |
|||
96×48size |
T1~T2 |
1~2Point alarm relay output, all with normally open contacts |
|||
track/transmitter output |
A1 |
current output(4~20)mAThe(0~10)mAThe(0~20)mA |
Photoelectric isolation, Resolution:1/10000Load capacity:600Ω |
||
A2 |
voltage output(0~5)VThe(1~5)V |
||||
A3 |
Voltage output(0-10)V |
||||
|
communication interface |
MS1 |
RS232interface |
Photoelectric isolation, Response time: less than500μS(Measurement value) Communication protocol selected through software |
||
MS2 |
RS485interface |
||||
Status signal output |
D |
1Point relay output, normally open contact,250V AC/3A, resistive load |
|||
External signal input |
K |
1Point externalPassive contact switch signal, used forControl hand/Auto Status |
|||
Æ note*:The optional specifications only describe the functions of the instrument selection. For detailed guidance on selecting instrument models, please refer to the instrument selection sample.